Customer
Large IOU
Location
Matthews, NC
Highlights
-
Arc Flash Risk Prevented by Fast, Safe Action
-
Procedural Weakness Prompted Immediate Review
-
Zero Downtime and Reinforced Safety Protocols
Unsecured Elbow Found During UG Transformer Inspection
The Challenge
During a routine service call for a "no power to meter" issue, a lineman discovered that the underground transformer was not energized. As part of his diagnostic process, the lineman inspected nearby transformers and identified the root cause: an elbow connector had backed off the primary bushing and was floating loose inside the transformer. This posed a significant risk of arc flash or electrocution had the component become live during inspection. Although no incident occurred, the situation exposed a critical weakness in elbow installation procedures and inspection protocols.
The Solution
The lineman immediately contacted the Distribution Control Center (DCC), secured the proper equipment, and used a shotgun stick to safely reseat the elbow onto the primary bushing. Fortunately, the event concluded without injury or service delay.
Key Benefits
- Incident Avoided Through Proper Procedure: The lineman used proper tools and safety procedures to prevent escalation.
- Hazard Identification Improved: The discovery prompted a review of recent installations and emphasized the need for final connection checks.
- Client Continuity Maintained: The issue was resolved with minimal downtime for the customer.
The Results
- Risk Contained: No injuries or equipment damage occurred.
- Lessons Captured: The event prompted reminders to crews to double-check elbow seating and to avoid overusing silicone, which may impair proper contact.
- PPE Reinforcement: The importance of wearing full PPE during UG transformer access was reiterated across teams.